FP2 CPU
|
|
The FP2 offers top performance and a full range of functions at just 36% of the volume of comparable controllers.
Combination CPU with integrated performance - Standard CPUs - CPU with integrated S-LINK - Combination CPU with 64 inputs
Up to 28 modules or 1600 (2048) inputs and outputs The system allows standard backplanes for 5, 7, 9, 12 or 14 modules to be combined, yielding a total of up to 1600 inputs and outputs (2048 via remote I/O).
Two RS232C interfaces (TOOL port and COM port) included as standard in the CPU - Simple communication with operation display panels or a host PC - 115.2kbit/s max. data rate - Telecontrol via modem and full remote access functionality
|
 |
 |
| Performance specifications |
|
|
 |
 |
 |
| PLC type |
FP2-C1 |
FP2-C1D |
FP2-C1SL |
| |
Standard type CPU unit |
64-point input CPU unit |
S-Link CPU unit |
| Inputs/outputs |
Central: max. 1600 (with 25 modules) Locally expanded: max. 2048 (via MEWNET-F or S-LINK) |
| Memory |
RAM (EPROM or FROM optional) |
| Programme memory |
16,000 steps, expandable to 32,000 steps |
| Number of instructions |
|
| basic instructions |
96 |
| high-level instructions |
428 |
| Operating speed |
0.35µs per basic instruction |
| Internal relay (R) |
4048 |
| Memory |
Timer/counter (T/C) |
1024 |
| Data register (DT) |
6000 words |
| File register (FL) |
0 to 14,333 words, optionally up to 30,717 words |
| Master control relay (MCR) |
256 |
| Jump labels (JMP + LOOP) |
256 |
Max. main memory programme steps |
1000 |
| Number of subroutines |
100 |
| Interrupt programme |
1 |
| Time interrupt |
0.5ms to 1.5s |
| Other functions |
Runtime editing, watchdog function, I/O error check, battery, syntax, memory and password functions, test mode, machine code memory, constant cycle time |
|
 |
 |
|
Expansion modules
|
|
|
 |
 |
|
Power supply modules
|
|
| P / N | Voltage | Rating (at 5V side) | | FP2-PSA1 | 100 - 120V AC | 2.5A | | FP2-PSA2 | 200 - 240V AC | 2.5A | | FP2-PSA3 | 100 - 240V AC | 5A | | FP2-PSD2 | 24V DC | 5A |
|
 |
 |
|
Input modules
|
|
| P / N | I/O Number | Voltage | Connection | | FP2-X16D2 | 16 | 12 - 24V DC | Terminal | | FP2-X32D2 | 32 | 24V DC | Connector | | FP2-X64D2 | 64 | 24V DC | Connector |
|
 |
 |
|
Output modules
|
|
| P / N |
I/O Number |
Voltage |
Connection |
| FP2-Y6R |
6 relay |
250V AC / 5A |
terminal |
| FP2-Y16R |
16 relay |
250V AC / 2A |
terminal |
| FP2-Y16P |
16 transistor PNP |
12-24V DC / 0.5A |
terminal |
| FP2-Y16T |
16 transistor NPN |
12-24V DC / 0.5A |
terminal |
| FP2-Y32P |
32 transistor PNP |
12-24V DC / 0.1A |
connector |
| FP2-Y32T |
32 transistor NPN |
12-24V DC / 0.1A |
connector |
| FP2-Y64P |
64 transistor PNP |
12-24V DC / 0.1A |
connector |
| FP2-Y64T |
64 transistor NPN |
12-24V DC / 0.1A |
connector |
|
 |
 |
|
I/O mixed modules
|
|
|
| FP2-XY64D2T |
FP2-XY64D2P |
| Input |
32 |
| Voltage |
24V DC |
| Response time OFF-> ON |
0.3ms or less |
| Output |
32 |
| I/O number |
Transistor NPN |
Transistor PNP |
| Voltage |
5 to 24V DC |
| Rating |
0.1A (12-24V DC) |
50mA (5V DC) |
|
 |
 |
|
Analogue modules
|
|
| Analogue input modules |
| P/N |
FP2-AD8X |
FP2-AD8VI |
FP2-RTD |
| Input range |
+/-100mV, +/-10V, 1-5V, thermocouples, RTD |
+/-10V, 1-5V, +/-20mA, 4-20mA |
Pt100, JPt100, JPt1000 |
| Conversion speed |
500µs/ch voltage 20ms/ch temp. |
500µs/ch |
20ms/ch |
| Accuracy |
+/-0.1% Voltage +/-0.3% V temp. |
+/-1.0% |
+/-0.3% |
| |
| Analogue output module |
| P/N |
FP2-DA4 |
| Outputs |
4 |
| Output range |
-10V to +10V, 0 to 20mA |
| Conversion speed |
500µs/ch |
| Accuracy |
+/-1.0% (at 0 to 55°C) |
Twenty types of input range such as voltage and temperature sensor are selectable and available for various connection devices (FP2-AD8X). RTD device and thermocouple can be directly connected (FP2-AD8X, FP2-RTD).
|
 |
 |
|
Positioning modules
|
|
For system-integrated 2- and 4-axis path control. Maximum 4Mpps command yields high-speed and high-precision positioning. 0.005ms high-speed drive reduces tact time. Feedback pulse count function makes output pulse counting possible for encoders, etc. JOG positioning control supports a wide range of applications. | Product number | Specifications | | FP2-PP21 | Transistor output, 2 axes | | FP2-PP41 | Transistor output, 4 axes | | FP2-PP22 | Line driver output, 2 axes | | FP2-PP42 | Line driver output, 4 axes |
|
 |
 |
|
High-speed counter and pulse I/O modules
|
|
| High-speed counter modules |
| Counter |
4 channels, max. 200kHz |
| Interrupt input |
8 points |
| Calculation range |
32-bit |
| |
|
|
| P / N |
FP2-HSCP |
FP2-HSCT |
| Input type |
PNP |
NPN |
| |
|
|
| Pulse I/O modules |
| Counter |
4 channels, max. 200kHz |
| Interrupt input |
8 points |
| PWM output |
4 points: 1Hz to 30kHz |
| Pulse output |
4 points: 100kHz |
| |
|
|
| P / N |
FP2-PXYP |
FP2-PXYT |
| Output type |
PNP |
NPN |
|
 |
 |
|
Multi communication unit
|
|
The FP2-MCU module enables quick and efficient data exchange between Panasonic's FP2 series PLCs and other automation systems. Detachable interface modules make it easy to connect an FP2 PLC to a variety of serial communications devices such as operator terminals, sensor systems, vision systems, temperature controllers, remote maintenance or diagnostic systems or to additional PLCs. - Fast communication speeds of up to 230Kbps
- Communication protocol options including RS232C, RS422 or RS485
- Double isolation of the communications channel
- Up to 19 modules can be connected in one system
- Transmission distances of up to 1200m can be achieved
|
 |
 |
|
FP2 Multi-wire link module and S-Link module
|
|
| FP2 multi-wire link module FP2-MW |
- PLC link function:
Enables data to be shared between programmable controllers, using cyclically transmitted link relays (L) and link registers (LD).
- Data transfer function:
Programmable controllers in the same system send and receive information pertaining to contacts and registers using the high-level instructions F145 and F146.
- Remote programming function:
The programming functions of a programmable controller can be used to program other programmable controllers in the same system, and for operations such as monitoring contacts and registers. |
| S-Link module FP2-SL2 |
- The S-Link unit is used by assigning inputs (X) and outputs (Y). The inputs/outputs on the FP2 side that result from these assignments are treated as I/O addresses (S-Link I/O devices in the S-Link).
- It controls up to 2,048 remote I/Os per FP2 system.
|
|
 |
 |
|
Ethernet-LAN module FP2-ET1
|
|
The FP2 ET-LAN module enables data exchange between different types of PLCs with a vendor-independent protocol and a short processing time. TCP/IP establishes logical point-to-point communication between two devices and provides the basis for exchanging information among all areas of production. You can connect 8 Ethernet segments with each other at a transmission speed of up to 100Mbits/s. Three communication interface types are supported: 10 BASE 5, 10 BASE-T, 100 BASE-TX.
|
 |
 |
|
Fieldbus Slave Units
|
|
Powerful, compact, modular and high performance fieldbus slave units (FSU) are used together with the programmable controllers FP2/FP2SH series. You can download all the slave data and convenient ready-made function libraries free of charge. The fieldbus slave units are available for PROFIBUS, DeviceNet, CANopen and Profinet IO. Others are planned for the future.
| FP2 Fieldbus Slave Units |
| Name |
Specifications |
Part no. |
| FP2 PROFIBUS DP Slave Unit |
PROFIBUS |
FP2-DPV1-S |
| FP2 DeviceNet Slave Unit |
DeviceNet |
FP2-DEV-S |
| FP2 CANopen Slave Unit |
CANopen |
FP2-CAN-S |
| FP2Profinet IO Device Unit |
Profinet IO |
FP2-PRT-S |
|
 |
 |
|
Fieldbus Master Units for PROFIBUS DP, CANopen and DeviceNet
|
|
The expansion Fieldbus Master Units (FMU) allow you to integrate FP2 PLCs as Master into your network with a maximum degree of flexibility. The units are available for three bus systems: PROFIBUS, DeviceNet and CANopen. For each network type, ready-made function libraries are available for the programming software Control FPWIN Pro. These libraries drastically shorten the time needed to develop your applications, and consequently save valuable human resource costs.
|
|